Lake Forest Electrician- Bath Electrics

By Frank Chang


The service panel is the central power distribution center after entering the house. In new construction or in houses that were built recently, the service entrance, in all likelihood be a circuit breaker protected from 150 amps to 200 amps 240 volts service. But the old houses are still often fuse boxes with either round or cartridge type fuses protecting circuits. There are many houses with 60 amps 120 volt wiring services, knob and tube, and only four circuits of 15 amps. This type of system is not inherently dangerous, in fact, more reliable than the fuse switches, but it is insufficient for most modern households and can mean a bathroom upgrade would require the upgrading of the system Electrical and potentially costly and probably unexpected add-on.

A 240 volt 100 amp service is probably little room for additional chips, if the switches in tow (two switches that fit in one place) can provide additional circuitry to update a bathroom. Panel with 150 amps or 200 amps generally have enough room for additional switches.

On a circuit protected by circuit breakers or fuses, and distributes electricity in different parts of the house. The demand for electrical circuits scaled to a specific branch. For example, lighting and general-purpose circuit house can be a 20 amp fuse, and be connected to the # 12 type NM (romex or the surface of the leather jacket) cable. Individual equipment, jacuzzi, for example, tend to require a single circuit. Sizing switches and wires guided by local building codes, which in turn are based on National Electric Code (NEC) published by the National Fire Protection Association. Local regulations may also allow only certain types of cables.

All furniture and appliances that use electricity is estimated amount of power they are using. This figure is measured in amperes (flow rate for electricity), and the device should be available technical literature, as only the device itself. This information is important for the design of piping bathroom because it determines the number of circuits are needed and their size. So it's important to know exactly what is going to the bathroom and either a lamp or in the technical literature rack (s) in hand before the design of the electrical layout. For example, there are some low-flow toilets that require an electrical outlet, and all of a sauna, whirlpool or steam units require more electrical power, and usually have their own circuit.

Another Code is the requirement that the light switches from a distance of less than 5 m from any type of tub or shower. This is to keep the switches away from a pool of water in feet. Taken, of course, is not allowed to bathe or shower (NEC 410-57), but the bathrooms need at least a GFCI (ground fault circuit interrupter) protected by a 20 amp outlet next to each sink (NEC 210 - 8). GFCI constantly compares the electrical current through the hot and neutral sides of the circuit and turns off almost immediately (less than a second 5/iooo) if the difference should be greater than 5 mA. All outlets in bathrooms and tubs are protected by circuit breakers (NEC 680-70), which can be installed on the service panel as the GFCI breaker or outlet same bath.

GFCI breakers are generally more expensive and less convenient to reset GFCIs trip as if I did, but they are less affected by excessive moisture, sometimes in a bathroom, which can cause false triggering of the circuit.

The code also requires that fixtures be used correctly rated in damp or wet from the bathroom. Most codes prohibit the track lighting bath. And cord-connected equipment which includes pendants, or ceiling fans, should not be placed directly over a bathtub or 3 m horizontally and vertically on top of 8 m at the edge of a bathtub (NEC 410-4) .




About the Author:



Grab The Post URL

URL:
HTML link code:
BB (forum) link code:

Leave a comment

  • Google+
  • 0Blogger
  • Facebook
  • Disqus

0 Response to "Lake Forest Electrician- Bath Electrics"

Post a Comment

comments powered by Disqus